FC2 – ELECTROMAGNETIC FLOW METER

 

Converter:

power supply
230V AC (+10%, -15%), 50Hz
15 to 24V AC / 12 to 34 V DC
power consumption
10VA max.
protection category
IP 67
operating temperature
0°C to +45°C (32 to 113°F)
measurement range
0,1 to 10m/s (0,02 to 5000l/s)
measurement error
≤ 0,2%of measured value within range of  5 to 100% Qmax.
indications
large permanently backlit graphical display
manual control
five buttons
output
(galvanically separated)
analogue current active
0 to 20mA or 4 to 20mA into load < 500Ω
2x multifunctional pulse or status
reley, load 125V ~ / 1A or 30V/2A
transistor NPN, load 30V/50mA
communication
RS232
casing material
Aluminium
weight
3Kg

Sensor:
DN
10 to 1200mm
conductivity of measured liquid
≥ 5μS.cm-1
casing
IP67 or IP68
lining
hard rubber
PTFE / E-CTFE
maximal temperature
of measured medium
hard hubber: 80°C (176°F)
PTFE: 150°C (302°F)
E-CTFE: 130°C (266°F)
PN
1,0 to 4,0MPa
electrodes
standart: stainless steel (AISI 316 TI)
chemically resistant: titanium, hastelloy, tantalum
flanges
flat, in line with: ČSN
  DIN
  ANSI
cable lenght
for remote design
5 to 30m

DATA SHEET in PDF